Free Online Calculator

Voltage Drop Calculator

Estimate the voltage drop of a copper or aluminum wire run from its size, length, load current and phase — in volts and percent.

Last updated: Free, no sign-up Private — runs in your browser

Voltage Drop Calculator

Estimate the voltage lost along a copper or aluminum wire run. Choose a wire size, or enter your own resistance data.

Quick answer: how to calculate voltage drop

Single-phase or DC: voltage drop = 2 × current × wire resistance per length × one-way length. Three-phase: √3 × current × resistance × length. Example: 12 AWG copper, 100 ft, 20 A, 120 V → about 6.35 V (5.3%).

Overview of the Voltage Drop Calculator

The Voltage Drop Calculator estimates how much voltage is lost along a cable run between the supply and the load. Enter the wire material and size (or your own resistance data), the source voltage, phase, load current and one-way distance, and it returns the voltage drop in volts and as a percentage, the voltage left at the load, and the power wasted as heat in the wire.

Excessive voltage drop makes lights dim or flicker, heaters under-perform and motors run hot. It matters most on long runs, such as feeding a workshop, borewell pump, outbuilding or solar array, and on low-voltage (12 V and 24 V DC) systems where a small loss is a large percentage. A common design guideline is to keep drop under about 3% on a branch circuit and about 5% overall, but always follow the standard that applies to your installation.

Important: this tool estimates resistive drop only. It does not check the wire's current-carrying capacity (ampacity), insulation, grouping or protective devices, and it ignores reactance. Have a qualified electrician confirm the final design.

How We Calculate Voltage Drop

  1. Find the wire's resistance. For a chosen AWG or kcmil size, the conductor's cross-section is taken from its geometry (AWG diameter = 0.127 mm × 92(36−n)/39); resistance per km = resistivity ÷ area. Copper uses 1.724 × 10⁻⁸ Ω·m and aluminum 2.82 × 10⁻⁸ Ω·m at 20 °C, corrected for the conductor temperature you enter. In “Custom resistance” mode your value is used directly.
  2. Account for the round trip. Current flows out and back, so a single-phase or DC circuit loses voltage over twice the one-way distance.
  3. Apply Ohm's law: single-phase or DC: Vdrop = 2 × I × R × L. Three-phase: Vdrop = √3 × I × R × L. Parallel conductors divide the drop by their number.
  4. Express it as a percentage of the source voltage and subtract it to find the voltage at the load.
  5. Estimate heat loss: I² × the resistance of the conductors carrying the current.
single-phase / DC: Vdrop = 2 · I · R · L ÷ n
three-phase: Vdrop = √3 · I · R · L ÷ n
R = resistivity ÷ conductor area (per unit length)   drop % = Vdrop ÷ Vsource × 100
I = load current (A), R = resistance of one conductor per unit length (Ω), L = one-way length, n = conductors per phase
Worked examples (20 °C conductor, resistive drop only)
CircuitVoltage dropDrop %
Single phase 230 V, 20 A, 30 m, copper 14 AWG (≈2.1 mm²)9.94 V4.32%
Single phase 230 V, 20 A, 30 m, copper 10 AWG3.93 V1.71%
Single phase 230 V, 20 A, 30 m, aluminum 10 AWG6.43 V2.80%
3-phase 415 V, 30 A, 200 m, copper 4 AWG8.47 V2.04%
3-phase 415 V, 30 A, 200 m, copper 1 AWG4.22 V1.02%
DC 12 V, 10 A, 5 m, copper 12 AWG0.52 V4.34%

Wire Size and Resistance Chart (AWG)

Estimated resistance of common wire sizes at 20 °C. Values for copper match published AWG tables to within about 0.1%.

Wire size, area and resistance
Wire sizeDiameter (mm)Area (mm²)Copper (Ω/km)Aluminum (Ω/km)
14 AWG1.632.088.28513.552
12 AWG2.053.315.2108.523
10 AWG2.595.263.2775.360
8 AWG3.268.372.0613.371
6 AWG4.1213.301.2962.120
4 AWG5.1921.150.8151.333
3 AWG5.8326.670.6461.057
2 AWG6.5433.630.5130.839
1 AWG7.3542.410.4070.665
1/0 AWG8.2553.480.3220.527
2/0 AWG9.2767.430.2560.418
3/0 AWG10.4085.030.2030.332
4/0 AWG11.68107.220.1610.263
250 kcmil12.70126.680.1360.223
500 kcmil17.96253.350.0680.111
1000 kcmil25.40506.710.0340.056

Acceptable Voltage Drop Limits

Common voltage drop guidelines
Circuit partCommonly cited limitWhy it matters
Branch circuit (final circuit)About 3%Keeps lights, appliances and motors performing normally
Feeder + branch combinedAbout 5%Overall limit from supply to the load
Low-voltage DC (12 V / 24 V)About 2–3%A 0.5 V loss is over 4% on a 12 V system

Guidelines vary by country and application. Check the wiring regulations or standard that applies to your installation.

How to Reduce Voltage Drop

  • Use a thicker wire. Every 3 AWG steps down roughly doubles the cross-section and halves the resistance.
  • Shorten the run or move the supply point closer to the load.
  • Use copper instead of aluminum for the same size — copper has about 39% lower resistance.
  • Increase the supply voltage. Doubling the voltage halves the current for the same power, which cuts the drop (and loss) sharply.
  • Use parallel conductors on large feeders.

Voltage Drop Calculator — Frequently Asked Questions

What is voltage drop?

Voltage drop is the loss of electrical potential along a conductor because the wire has resistance. The voltage at the load ends up lower than the supply voltage by V = I × R.

How do I calculate voltage drop?

For single-phase or DC: 2 × current × resistance per length × one-way length. For three-phase: √3 × current × resistance per length × one-way length. This calculator does the maths and also gives the percentage.

What is an acceptable voltage drop?

A common guideline is up to about 3% on a branch circuit and about 5% for the whole installation. Sensitive equipment and low-voltage DC systems often need less. Follow the standard that applies to you.

Why is the distance doubled for single-phase and DC circuits?

Current has to travel to the load and back, so the resistance that matters is that of two conductors of the one-way length.

Copper or aluminum — which has less voltage drop?

Copper. For the same size and length, aluminum's resistance is about 64% higher, so it needs a larger cross-section to match copper.

Does wire temperature matter?

Yes. Resistance rises with temperature — about 0.39% per °C for copper. A conductor at 75 °C has roughly 22% more resistance than at 20 °C. Enter the expected operating temperature for a conservative estimate.

How do I reduce voltage drop?

Use a larger wire, shorten the run, use copper, raise the supply voltage or use parallel conductors.

Does this calculator check if the wire is safe for the current?

No. It estimates voltage drop only. The wire must also have enough current-carrying capacity (ampacity) for the load and conditions, and be properly protected — consult a qualified electrician.

Does it include reactance or power factor?

No. This tool uses resistance only, which is accurate for DC and for most small AC circuits. For large AC conductors, power factor and reactance can change the result.

What is AWG?

American Wire Gauge is a standard for the diameter of round electrical wire. A smaller AWG number means a thicker wire; every 6 gauge steps doubles the diameter.

What does “conductors per phase in parallel” mean?

Large cables are often built from several smaller conductors run side by side per phase. The current is shared between them, so the drop is divided by their number.